1. Equipped with two-way temperature monitoring: can monitor the temperature of the isolation transformer at any time, and control the cooling fan and over temperature alarm according to the temperature setting value.
2、 Equipped with load monitoring: It can measure the output size of the load at any time and issue an overload alarm when the output is overloaded.
3、 Equipped with voltage monitoring: It can measure the system voltage value in real-time and issue corresponding overvoltage and undervoltage alarms based on the set voltage value.
4、 Equipped with insulation fault location function: When the insulation monitoring detects that the system insulation value is less than the set value, it determines that there is a grounding insulation fault in the system. At this time, according to the corresponding system configuration, a periodic test signal with an effective value of less than 1mA will be issued, and the insulation fault locator will be used to achieve precise positioning of the fault branch.
5、 Equipped with system wiring detection function: detect all wiring connections in the system and issue corresponding alarms in case of missing or incorrect connections.
6、 Having multiple communication interfaces: capable of networking with leakage testers to improve system configuration; It can be remotely monitored with the upper unit network.
7、 Composition of medical isolation power cabinet: medical isolation transformer, medical insulation monitoring device, dedicated power supply, external alarm display and testing device, insulation fault locator, leakage tester.